Increased safety lightings
18/20, 36/40 and 58/65W
fluorescent luminaires Zone: 1, 2 21 and 22
Approval : EC 0081 (EX) II 2G EExd IIC T4 / T5 Ta max +40°C
EC 0081 (EX) II 2 D T 85°C
Certificate: LCIE 98 ATEX 6004
Operating temperature:-20°C bis + 40°C IP 66/67
• Ø 38 mm (20, 40 and 65 W) and Ø 26 mm (20, 36 and 58 W)
• Ø 26 mm mono and bi-pin tubes, standard G13 lampholders
• Frequency : 50/60 Hz
• Power supply via high frequency ballast depending on version : 99 to 140V 110/127 V ±10% AC/DC or 220/240 V~ ±10%,
198 to 264 V Frequency: 50/60 Hz
•Instant start. Power factor ≥0.95
•Pre-impregnated fibre glass reinforced polyester body
•Polycarbonate multi-parabolic hinged reflector
•Polycarbonate diffuser hinged to body; Elastomer gasket
•High temperature internal wiring; Anti-vibration lampholders with spring system
•Separate operation of the tubes: if one tube fails, the other tube remainslit
•Power supply to the unit cut off by positive safety switch which operateswhen diffuser is opened, for replacing tubes with mains power switchedon
•Open and close using an Allen key or flat screwdriver (system automati-cally protects against over turning)
•IP 2X terminal strip cover for maintaining the ballast and lampholderswithout cutting off the main power supply
•Ballast fixed by screws, equipped with a fast connector
Ex e lightings in our webshop

Light for your plant
^To TOP
Flameproof lightings
18, 36 and 58 W fluorescent
luminaires
Zone: 1,2 21 and 22
Approval : EC 0081
(EX) II 2G Exd IIC T6
EC
0081 (EX) II 2 D T 85°C
Certificate: LCIE 97 ATEX 6012
Operating temperature:-20°C bis + 55°C IP 66/67
with ferromagnetic ballast
• Single and twin tubes
• Borosilicate glass sealed tube
• Zamak end caps and cover anticorrosion treated and painted grey
• Threaded access cover with O ring seal
• High temperature internal wiring
• Connection via 2 x 3 x 2.5 mm2 terminals
• Two 3/4 NPT threaded cable entries for 230 V and two M20 threaded
entries for 240 V version
• Supplied with a 3/4 NPT or M20 blanking plug (cable gland not
supplied)
• External earth via bracket : 4 mm2
• Operates in any position
Easy to install, easy to handle!
^To TOP
Emergency lighting (increased safety)
8, 36 and 58 W auto-test
fluorescent
luminaires for normal and
emergency
lighting
Zone: 1, 2 21 and 22
Approval : EC 0081
(EX) II 2G EExd IIC T4 / T5 Ta max +40°C
EC
0081 (EX) II 2 D T 85°C
Certificate: LCIE 98 ATEX 6004
Operating temperature:-20°C bis + 40°C IP 66/67
• Ø 26 mm mono and bi-pin tubes, standard G13 lampholders
• Frequency: 50/60 Hz
• Common power supply circuit to provide both normal lighting and
emergency
lighting
• Power supply via high frequency ballast 230/240 V~ ± 6%;216 to 256 V~
• Instant start - Power factor ≥ 0.96
• Battery voltage : 18W, 36W and 58W - 6V
• Pre-impregnated fibre glass reinforced polyester body; •
Polycarbonate multi-parabolic hinged reflector
• Polycarbonate diffuser hinged to body
• High temperature internal
wiring
• Elastomer gasket
• Anti-vibration lampholders with spring system
• Power supply to the unit (mains supply and battery) cut off by two
positive
safety switches which operate when diffuser is opened, for replacing
tubes with mains power switched on
• Operation : mains power switched on : 2 tubes lit
mains power switched off : 1 tube lit (battery backed)
• Automatic tests controlled by microprocessor:
– monthly : discharge for 5 minutes
– 6-monthly : discharge for 1 hour
– annual : discharge for 3 hours with indication (upon request) of
the number of months remaining before the next test
• In the event of a fault:
– LED flashes
– Buzzer emits 3 long beeps every 35 minutes until the repair is carried
out
• Battery-backed tube identified with green mark
• Open and close using an Allen key or flat screwdriver (system
automatically
protects against over turning)
• battery pack easily interchangeable on site, fixed by screws and
equipped
with a fast connector
• Ballast and converter fixed by screws, equipped with a fast connector
Light for your Emergency: safe and bright
^To TOPIIB - IIC wellglass luminaires (flameproof)

Zone: 1, 2 21 und 22
Approval : EC 0081
(EX) II 2G EExd IIC T* (depending on power of lamp)
EC
0081 (EX) II 2 D T *(depending on power of lamp
Certificate: LCIE 02 ATEX
6165
operating temperature:-40°C bis + 55°C IP 66/67
• Compensated power supply 230/240 V (± 10%) 50 Hz
• For 85W induction: power supply 230/240 V (+ 6% - 10%) 50/60 Hz
• Power
factor ≥ 0.9
• Grey painted marine grade aluminium alloy body and bezel
•
Internal aluminium reflector
• Sealed shock resistant wellglass. IIB version
hinged
• Flat joint for IIB version, threaded on IIC version
• E 40 lampholder
with lock thread
• High temperature internal wiring
• Operates in any
position subject to lamp type
• Connection in increased safety “e” compartment
to terminal block via
two 2 x 6 mm2 self-tightening terminals or 6 mm2 terminals
(with lug not
supplied) + 1 earth terminal per cable entry (4 mm2)
• External
earth: 4 mm2
• Two lateral threaded entries via M20 cable gland
• Supplied
with:
– One M20 non armoured cable gland (sealed Ø 6.5 to 14.5 mm)
–
One M20 blanking plug
For all appilcations